|











|
|

Frequently
Asked Questions
Requirement 1
Q. When would it be considered impractical to provide
an accessible entrance served by an accessible route due to terrain?
A. The Accessibility Guidelines provide an impracticality
standard only for non-elevator buildings. Buildings with elevators must
be designed to provide at least one accessible entrance on an accessible
route. A covered multifamily dwelling without an elevator shall be designed
and constructed to have an entrance on an accessible route unless the
characteristics of the site are impractical, as determined by one of two
alternative tests, described below as Test 1 and Test 2. The tests may
be applied as follows:
A site with a single building having a common
entrance for all units may be analyzed only as described under Test 1.
All other sites, including a site with a single building having
multiple entrances serving either individual dwelling units or clusters
of dwelling units, may be analyzed using the methodology in either Test
1 or Test 2.
EXCEPTION: For sites for which either test is applicable,
regardless of which test is selected, at least 20% of the total ground
floor units, on any site, must comply with the Guidelines.
Test 1 - Individual Building Test - It is impractical
to provide an accessible entrance served by an accessible route when the
terrain of the site is such that:
(A) the slopes of the undisturbed site measured between the planned
entrance and all vehicular or pedestrian arrival points within 50 feet
of the planned entrance exceed 10 percent; and (B) the slopes of
the planned finished grade measured between the entrance and all vehicular
or pedestrian arrival points within 50 feet of the planned entrance exceed
10 percent.
Note: If there are no vehicular or pedestrian arrival
points within 50 feet of the planned entrance, the slope for the purposes
of Test 1 will be measured to the closest vehicular or pedestrian arrival
point.
Test 2 - Site Analysis Test - For a site having multiple buildings, or
a site with a single building with multiple entrances serving either individual
dwelling units or clusters of dwelling units, impracticality can be established
by the following steps:
(A) The percentage of the total buildable area
of the undisturbed site with a natural grade less than 10% slope shall
be calculated. The analysis of the existing slope (before grading) shall
be done on a topographic survey with two foot (2') contour intervals with
slope determination made between each successive interval. The accuracy
of the slope analysis shall be certified by a professional licensed engineer,
landscape architect, architect or surveyor. (B) To determine the
practicality of providing accessibility to planned multifamily dwellings
based on the topography of the existing natural terrain, the minimum percentage
of ground floor units to be made accessible should equal the percentage
of the total buildable area (not including floodplains, wetlands, or other
restricted use areas) of the undisturbed site that has an existing natural
grade of less than 10% slope. (Note: Of course the previously mentioned
exception still applies, i.e., at least 20% of the total ground floor
units, on any site, must comply with the Guidelines. (C) In addition
to the percentage established in paragraph (B), all ground floor units
in a building, or ground floor units served by a particular entrance,
shall be made accessible if the entrance to the units is on an accessible
route, defined as a walkway with a slope between the planned entrance
and a pedestrian or vehicular arrival point that is no greater than 8.33%.
Q. When would it be considered impractical to provide
an accessible entrance served by an accessible route due to unusual characteristics
of the site?
A. Unusual characteristics include sites located in a Federally-designated
floodplain or coastal high-hazard area and sites subject to other similar
requirements of law or code that the lowest floor or the lowest structural
member of the lowest floor must be raised to a specified level at or above
the base flood elevation. An accessible route to a building entrance is
impractical due to unusual characteristics of the site when:
(1) the unusual site characteristics result in a difference in finished
grade elevation exceeding 30 inches and 10 percent measured between an
entrance and all vehicular or pedestrian arrival points within 50 feet
of the planned entrance; or
(2) if there are no vehicular or pedestrian arrival points within 5 feet
of the planned entrance, the unusual characteristics result in a difference
in finished grade elevation exceeding 30 inches and 10 percent measured
between an entrance and the closest vehicular or pedestrian arrival point.
Q. Who bears the burden of establishing impracticality?
A. The burden of establishing impracticality because of terrain or usual
site characteristics is on the person or persons claiming site impracticality.
This means that, when a complaint is filed, the burden is first upon the
person(s) claiming site impracticality to demonstrate how he/she determined
that the project site met the impracticality criteria contained in the
Guidelines. Once the basis for the impracticality determination is established,
the burden shifts to the complainant to demonstrate that the builder's
methodology or calculations were unsound or flawed.
Q. Under Test 1, how is the slope of the site calculated?
A. To determine the slope of a site, the distance and
elevation between two points (e.g. an entrance and a pedestrian or vehicular
arrival point) are determined. The difference in elevation is divided
by the distance and that fraction is multiplied by 100 to obtain a percentage
slope figure. For example, if a principal entrance is ten feet from a
pedestrian arrival point and the principal entrance is raised one foot
higher than the pedestrian arrival point, then the slope is l/lOxlO0=10%.
Q. A developer plans to construct a 100-unit apartment
building with one elevator. Must all 100 units be accessible?
A. Yes. A 100-unit apartment would be a covered multifamily dwelling under
the Fair Housing Act. Under the Accessibility Guidelines an elevator building
must provide at least one accessible entrance on an accessible route,
regardless of terrain or unusual characteristics of the site. Therefore,
all 100 units must be designed and constructed so that they comply with
the accessibility requirements of the Fair Housing Act.
Q. A developer plans to construct 30 apartments in
a three story building that will not have an elevator. The building will
have one accessible entrance on the first floor. Must all of the apartments
be accessible?
A. No. Since the building does not have an elevator,
only the "ground floor" units are subject to the Act. The ground
floor is the first floor because that is the floor that has an accessible
entrance. Unless impracticality is established, as discussed above, all
of the dwelling units on the first floor must meet the Act's requirements;
and there must be at least one of each type of public or common use area
available for residents with disabilities in the building. Even where
impracticality has been established, a minimum of 20% of the total ground
floor units in nonelevator buildings, on any site, must comply with the
Guidelines, unless it is a site with a single building having a common
entrance for all units.
Q. Can a building have more than one "ground floor?"
A. Yes. Each floor of a covered multiple family dwelling
that has an accessible route leading to an accessible entrance is considered
a "ground floor.
Q. If a covered multifamily dwelling has more than
one common entrance, must all such entrances be on an accessible route
?
A. No. Only one common entrance is required to be accessible
to any one ground floor of a building, except in cases where an individual
dwelling unit has a separate exterior entrance, or where the building
contains clusters of dwelling units, with each cluster sharing a different
exterior entrance. In those cases, more than one entrance may be required
to be accessible, as determined by analysis of the site. In every case,
the accessible entrance should be on an accessible route to the covered
dwelling unit(s) it serves.
Q. A developer is planning to construct a project that consists of several
buildings. Must each building contain an accessible building entrance
on an accessible route?
A. Yes. Each building on a site shall have at least
one building entrance on an accessible route unless prohibited by the
terrain or unusual characteristics of the site. Further, if the building
has one or more elevators, then the building must include an accessible
entrance on an accessible route, regardless of terrain or unusual characteristics
of the site.
Q. A developer is constructing 10 three-story nonelevator
buildings on a site. Each building has one common entrance. The developer
conducts a site analysis according to Test 2, and the results show that
60% of the ground floor units must meet the FHA's requirements. The builder
plans to meet the 60% requirement by providing an accessible entrance
for six of the 10 buildings. However, according to the finished plans,
two of the four inaccessible buildings have a walkway leading from the
sidewalk to the entrance which has a slope of 8%. Must these two buildings
be accessible?
A. Yes. Under Test 2, after the minimum percentage
of accessible units has been determined, a building must still provide
accessibility in the ground floor units if the entrance to the building
is on an "accessible route." Such an accessible route is defined
as a walkway with a slope between the planned entrance and a pedestrian
or vehicular arrival point that is no greater than 8.33%.
Q. A developer is planning to construct a single building
on a very hilly site. The building will have a parking area connected
to the ground floor dwelling units by an elevator. There is a second floor
of dwelling units accessed only by stairs. The finished grade of the site
will exceed 10 percent leading to the exterior front door and the service
entrances. Is the building exempt because of site impracticality?
A. No. Regardless of site considerations, an accessible entrance on an
accessible route is practical when there is an elevator connecting the
parking area with dwelling units on a ground floor. Thus, the dwelling
units on the ground floor, plus one of each type of public and common
use area, would be subject to the Guidelines.
Q. If a builder includes an elevator from a parking
garage to the ground floor only, and this elevator does not serve floors
other than the ground floor, is the building an "elevator" building?
A. No. Inclusion of an elevator to provide a means
of access from the garage to dwellings on the ground floor is not considered
an elevator building for purposes of the Guidelines; hence only the ground
floor units are covered.
Q. What is an arrival point to a building?
A. A pedestrian or vehicular arrival point includes
public or resident parking areas; public transportation stops; passenger
loading zones; and public streets or sidewalks.
Q. Under Test 1 (the individual building test) the
analysis considers the distance from the arrival point to the entrance.
How is this distance to be measured?
A. Under Test 1 the slope should be measured at ground
level from the point of the planned entrance on a straight line to (i)
each vehicular or pedestrian arrival point that is within 50 feet of the
planned entrance, or (ii) if there are no vehicular or pedestrian arrival
points within that specified area, the vehicular or pedestrian arrival
point closest to the planned entrance. In the case of sidewalks, the closest
point to the entrance will be where a public sidewalk entering the site
intersects with the sidewalk to the entrance. In the case of resident
parking areas, the closest point to the planned entrance will be measured
from the entry point to the parking area that is located closest to the
planned entrance.
Q. A developer is designing a single nonelevator building
with one common entrance to be located in the center of a large piece
of property with very hilly terrain. The land immediately around the planned
building site is relatively flat; but the grade of the land between the
building site and the two planned arrival points within 50 feet of the
entrance-public sidewalk and parking lot-exceeds 10 percent. (The other
arrival points are further away than 50 feet, and thus are not considered
under Test 1.) Is the building exempt from having an accessible entrance
on an accessible route?
A. A single building on a site with one common entrance
serving all dwelling units may only be analyzed under Test 1. In this
case, if the slopes of both the undisturbed site and the planned finished
grade between the building entrance and all pedestrian or vehicular arrival
points within 50 feet of the planned entrance exceed 10 percent, then
the building is exempt.
Q. A builder has conducted a site analysis for a single
non- elevator building on a site having one common entrance. The closest
vehicular and pedestrian arrival point is the sidewalk beside a driveway
that curves up a slope to a flat area in front of the building entrance.
The slope between the entrance and the sidewalk where the sidewalk intersects
the walk leading to the entrance is less than 10 percent. However, the
slopes between the entrance and all other vehicular and pedestrian arrival
points exceed 10 percent. Because of the slope the builder can not provide
an accessible pedestrian route from the parking lot. Is the building exempt
from coverage?
A. No, the building is not exempt, since an accessible entrance on an
accessible route, i.e. from the walk directly in front of the entrance,
is possible. However, the Guidelines provide that if the slope of the
finished grade between covered multifamily dwellings and a public or common
use facility (including parking) exceeds 8.33 %, or where physical barriers
(natural or manmade) or legal restrictions, all of which are outside the
control of the owner, prevent the installation of an accessible pedestrian
route, an acceptable alternative is to provide access via a vehicular
route, so long as necessary site provisions such as parking spaces and
curb ramps are provided at the public or common use facility.
Return to Requirement 1
The
IDEA Center
is the home of the RERC
on UD
at Buffalo
|